# Configuration

Note:Before starting configuration, a new module instance must be created .[Click here for more information about creating Module instances](/v122/docs/platform-create-new-module-instance).

## Module Configuration

![Figure 1- Channel Creation](https://cdn.document360.io/54093ab5-6b22-4542-a265-04377931f11a/Images/Documentation/Figure%201-%20Channel%20Creation.png)Figure 1. Channel Creation

As shown in the previous screenshot, multiple connections****can be created in the Model Panel by clicking on the burger menu icon. Each connection is named **Channel**. See below for an explanation of the different configuration options.

## Channel Configuration

A channel represents the physical medium of connecting one device. Each channel has the following parameters:

- **Data collection:** When disabled, the connection will remain inactive. The default value is set to Enabled.
- **Timing:**
  - **Request Timeout:** Maximum amount of time to wait for a valid response, displayed in milliseconds. The valid range is 100ms to 600,000ms. The default value is set to 3,000ms.
  - **Inter-request Delay:** Delay before sending subsequent requests to the target device, displayed in milliseconds. The valid range is 0ms to 600,000ms. The default is 0ms.****
- **Connection:**
  - **Type:** Specifies the connection type that will be established:
    - **TCP**
    - **Serial**

When connecting via**TCP,** the following options are displayed:

- **Modbus Mode:**Specifies the Modbus working mode:
  - **TCP:**Modbus TCP.
  - **RTU encapsulated:**Modbus RTU encapsulated over TCP.
- **Config**
  - **Host:** Hostname or IP address of the target device.
  - **TCP port:**Determines which TCP Port to connect to. Valid values range from 1 to 65535.
  - **Reconnect delay:**Time before trying to re-open the connection after a failed attempt, displayed in milliseconds. The minimum value is 1,000ms.

Whereas, **Serial**channels include the following <meta charset="utf-8">available options:

- **Modbus Mode:**Specifies the Modbus working mode. In this case, there is only one option:
  - **RTU:**Modbus RTU.
- **Config**
  - **Port name:**Serial port as displayed by the operating system. For example, if **N3uron** is running on Windows, valid port names would be COM1, COM2, and so forth. If running on Linux, valid port names would be /dev/ttyS0, /dev/ttyS1, and so forth.
  - **Reconnect delay:** Time before trying to re-open the serial port after a failed attempt, displayed in milliseconds. The minimum value is 1,000ms.
  - **Port settings:**
    - **Baud rate:** Serial port transfer speed in milliseconds. Valid values are 110, 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200.
    - **Data bits:**Specifies the number of data bits per data word. Valid values are 5, 6, 7, or 8.
    - **Stop bits:**Specifies the number of stop bits per data word. Valid values are 1 or 2.
    - **Parity:**Specifies the type of parity for data. Valid values are None, even, mark, odd, or space.
    - **Flow Control:** Enables the use of RTS and DTR control lines. There are 3 options: None, RTS/CTS (RS232), and RTS (RS485/RS422).
    - **Buffer size:**Specifies the Serial communication buffer capacity. The valid range is 128 to 65536.

## TCP Server Configuration

Regardless of the type of connection, Serial or TCP, a device (Channel) can have as many TCP Servers as needed.

As shown in the image below, to create a new TCP Server click on the ellipsis button and select **New TcpServer**.

![Figure 2- TCP Server configuration](https://cdn.document360.io/54093ab5-6b22-4542-a265-04377931f11a/Images/Documentation/Figure%202-%20TCP%20Server%20configuration.png)Figure 2. TCP Servers creation

Available configuration options for **TCP Servers** include:

- **TCP Port:**Specifies the port number for incoming connections. The valid range 1 to 65535, the default value is 3005.

Note:Make sure the port number is not used by any other application.

- **Network Interface:** Specifies the interface via which the **TCP Server** will be accessible. If set to 0.0.0.0, the **TCP Server** will listen to connections on all interfaces. If set to 127.0.0.1 or localhost, the **TCP Server** will only listen to local applications. In addition to the above options, the IP address for a specific network interface can also be set to only allow connections from that interface.

Note:In order to allow incoming connections from a specific network card, users will need to enter its IP address.

- **Modbus Mode:** Defines the connection mode. The available options are:
  - TCP
  - RTU encapsulated
- **Priority:** The priority of this **TCP Server** over the rest of **TCP Servers**on this channel. The valid range is 1 (highest priority) to 10 (lowest priority). The priority must be different for each gateway sharing the same channel. The default value is 1.
- **Max. connections:** The maximum number of TCP clients supported by this server. Set to 0 to disable the limit.

![Figure 3- TCP Connection Configuration](https://cdn.document360.io/54093ab5-6b22-4542-a265-04377931f11a/Images/Documentation/Figure%203-%20TCP%20Connection%20Configuration.png)Figure 3. TCP connection configuration

![Figure 4- Serial connection configuration](https://cdn.document360.io/54093ab5-6b22-4542-a265-04377931f11a/Images/Documentation/Figure%204-%20Serial%20connection%20configuration.png)Figure 4. Serial connection configuration