--- title: "Siemens Client | Introduction | N3uron KB V1.22" slug: "siemens-client-introduction" description: "Siemens Client is a N3uron module designed to provide connections to S7 Siemens PLCs. N3uron connects to these PLCs via TCP/IP using the S7 protocol…" updated: 2025-09-30T15:55:32Z published: 2025-12-23T10:13:13Z canonical: "docs.n3uron.com/siemens-client-introduction" --- > ## Documentation Index > Fetch the complete documentation index at: https://docs.n3uron.com/llms.txt > Use this file to discover all available pages before exploring further. # Introduction The **Siemens Client module** supports basic connections to S7 **Siemens** PLCs. **N3uron** connects to these PLCs via TCP/IP using the S7 protocol. Currently, **N3uron** can connect to the following **Siemens** PLCs: - S7 300 - S7 400 - S7 1200 - S7 1500 **Considerations for connecting to S7-1200 and S7-1500:** The following considerations and configuration changes must be made when connecting to the **S7-1200** and **S7-1500** devices: - The optimized block access must be turned off. ![](https://cdn.document360.io/54093ab5-6b22-4542-a265-04377931f11a/Images/Documentation/SiemensClientOptimizedBlock.gif) - The access level must be "full" and the "connection mechanism" must allow **PUT/GET**. ![](https://cdn.document360.io/54093ab5-6b22-4542-a265-04377931f11a/Images/Documentation/SiemensClientPutget.gif)